Devireg 535
Installation manual
Warning!
This manual is only to be used by a
professional installer to install and
set up the thermostat properly.
It is not intended for the end-user!
INT
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Devireg™ 535

Devireg™ 535Installation manualWarning!This manual is only to be used by a professional installer to install and set up the thermostat properly.It i

Page 2 - Congratulations with…

10Operation voltage 180-250 VAC, 50/60 HzStandby power consumptionMax. 0.30 WRelay: • Resistive load• Inductive load230V ~ 15A / 3450Wcos φ= 0.3 Max.

Page 3

INT11Disposal Instruction

Page 4 - Installation and connection

Article No.: 08095880Version - 02VICKI302 06/2010DEVI A/S Ulvehavevej 61DK-7100 Vejle Tel: +45 74 88 85 00Fax: +45 74 88 85 01www.devi.com

Page 5 - Choose sensor combination

2... your DEVI floor heating system.Your property has been installed with a DEVI electric floor heating system. DEVI is Europe’s leading floor heating ma

Page 6 - Configuration - sensor

INT3Placement of Devireg™ 535When Devireg™ 535 is used as a room sensor, installation height should typi-cally be between 80-150 cm.In wet rooms it sh

Page 7 - ▲▼ for the next setting

4N LInstallation of Devireg™ 5351. To remove the front cover, gently press the release tabs under the bottom of the thermostat with a screwdriver

Page 8 - Configuration - Scale

INT53. Choose sensor combination When installing the Devireg™ 535 you need to choose the type of heating and thus which sensors should be used

Page 9 - Trouble shooting

6Selection of sensor typePower on the thermostat.With the front off, with a small screw-driver, pencil, or needle press the installation button.Select

Page 10 - Technical specifications

INT7Notice:The floor temperature is measured where the sensor is placed. The temperature of the bottom of a wooden floor can be up to 10 degrees higher

Page 11 - Disposal Instruction

8ScaleIf you select DeviregTM 535 to only use a floor sensor, mode , you have to select the display type. The choice is either numerical scale 1-6 or

Page 12 - Version - 02

INT9Trouble shootingClock symbol flashing:Time settings were lost due to power cut.The thermostat resumes to manual mode.E4 flashing in display: Error c